Item # 70S2-05-C-03-V, 70S2 Series Solid State Relays/3, 5 Amp, V Style
70S2 Series Solid State Relays/3, 5 Amp, V Style
The 70S2 Series relays have excellent thermal performance and are designed for medium-power loads. Its compact size makes it ideal for designs where
space is limited. The design incorporates a triac output for AC loads and MOSFETs for DC loads. Optical isolation protects the control from transients. The
70S2 is available in a combination of screw, fast-on or PCB terminals.
SPECIFICATIONS
·
OUTPUT CHARACTERISTICS
·
INPUT CHARACTERISTICS
·
PERFORMANCE
CHARACTERISTICS
·
ENVIRONMENT
·
MISCELLANEOUS CHARACTERISTICS
·
PRODUCT
CERTIFICATIONS
SPECIFICATIONS
Component Type
Mounting Type
Rated Current Load
Contact Configuration
Control Voltage
Load Type
Input Voltage Range
Output Voltage Range
Solid State
PCB Mount
3A
SPST-NO
DC
DC
6 to 32 VDC
24 to 280 VAC
5/21/2008 | Page 1 of 3
Switching Type
Zero Cross
OUTPUT CHARACTERISTICS
Switching Device
Current Rating
Switching Voltage
Maximum Rate of Rise Off State Voltage [dv/dt]
Min. Load Current to Maintain On
Non-Repetitive Surge Current (1 cycle)
Max. Off State Leakage Current [rms]
Minimum Peak Blocking Voltage
Typical On State Voltage Drop [rms]
Triac
3A
24 to 280 VAC
300 V/us
75 mA
60 A
6 mA
600 VAC
1.6 VAC
INPUT CHARACTERISTICS
Voltage Range
Must Release Voltage
Typical Input Current at 5VDC or 240VAC
Maximum Reverse Control Voltage
6 to 32 VDC
1 VDC
1 to 6 mA
3 VDC
PERFORMANCE CHARACTERISTICS
Electrical Life (UL508), Operations at Rated Current
(Resistive)
Mechanical Life, Unpowered
Operating Time (Response Time) - On
100000
10000000
8.3 ms
µs
8.3 ms
µs
4000 VAC
Operating Time (Response Time) - Off
Dielectric Strength, Terminals to Chassis
ENVIRONMENT
Ambient Air Temperature around the Device - Storage
Ambient Air Temperature around the Device - Operation