首页 > 器件类别 > 电路保护 > 电路保护

069NH0K0125F

Electric Fuse, 125A, 690VAC, 690VDC, 170000A (IR), Inline/holder

器件类别:电路保护    电路保护   

厂商名称:IXYS

下载文档
器件参数
参数名称
属性值
厂商名称
IXYS
Reach Compliance Code
unknown
Is Samacsys
N
其他特性
RATED BREAKING CAPACITY AT 690 VDC: 170000 A
主体宽度
29.5 mm
主体高度
66 mm
主体长度或直径
59.5 mm
内置特性
INDICATOR
电路保护类型
ELECTRIC FUSE
焦耳积分标称
720 J
制造商序列号
069NH0K
安装特点
INLINE/HOLDER
物理尺寸
59.5mm x 29.5mm x 66mm
额定分断能力
170000 A
额定电流
125 A
额定电压(交流)
690 V
额定电压(直流)
690 V
参考标准
IEC; UL; VDE
表面贴装
NO
端子形状
TAB/BLADE
Base Number Matches
1
文档预览
Date:- 18 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
European Square Body Type
German Standard Knife Blade
aR Characteristics
Voltage Rating 690V
Current Ratings from 16A to 1000A
Sizes 000, 00, 0, 1, 2 & 3
Key Features:
Extremely high interrupting rating fuses for the protection of power semiconductors as per
IEC Standard 60269.1 and 4
690V voltage rating complying with IEC 33
Non Magnetic construction
aR Characteristics (current ratings from 16A to 1000A) as per VDE 636-23 and IEC 269.4
All models with double indication visual on the top and integrated trip-indicator
Microswitch system reference MS 4L 2-5 B+PRES
Data Sheet. 069NHxKxxxxF
Issue 1
Page 1 of 10
March, 2005
WESTCODE
An
IXYS Company
European Square Body Fuse – Knife Blade
Main Characteristics:
Size
Voltage
U
N
(V)
Ref:
069NHCK0016F
069NHCK0020F
069NHCK0025F
069NHCK0032F
069NHCK0040F
069NHCK0050F
Current
Micro Switch
rating I
N
(A)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
16
20
25
32
40
50
63
80
100
125
160
200
250
315
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
10
15
22
45
69
107
220
350
720
1400
2100
3900
7600
15400
Total
Clearing
I
2
t @ U
N
(A
2
s)
48
90
130
270
400
630
1300
2000
4300
8200
12200
22700
44400
90700
Power
Losses
@ 0.8 In
1
1.5
2
2.5
4
5
6
8
9.5
10.5
15
18
22
30
Tested
Interrupting
rating
000
690V
069NHCK0063F
069NHCK0080F
069NHCK0100F
069NHCK0125F
069NHCK0160F
069NHCK0200F
069NHCK0250F
069NHCK0315F
80kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 4L 2-5B6
Size
Voltage
U
N
(V)
Ref:
069NHDK0020F
069NHDK0025F
069NHDK0032F
069NHDK0040F
069NHDK0050F
069NHDK0063F
Current
Micro Switch
rating I
N
(A)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
20
25
32
40
50
63
80
100
125
160
200
250
315
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
15
22
45
69
110
220
350
720
1390
2100
3900
7600
15400
Total
Clearing
I
2
t @ U
N
(A
2
s)
90
130
270
400
630
1300
2000
4300
8200
12200
22700
44400
90700
Power
Losses
@ 0.8 In
1.5
2
2.5
4
5
6
8
8.5
10
14
17
20
29
Tested
Interrupting
rating
00
690V
069NHDK0080F
069NHDK0100F
069NHDK0125F
069NHDK0160F
069NHDK0200F
069NHDK0250F
069NHDK0315F
170kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 4L 2-5B6
Data Sheet 069NHxKxxxxF Issue 1
Page 2 of 10
March, 2005
WESTCODE
An
IXYS Company
European Square Body Fuse – Knife Blade
Size
Voltage
U
N
(V)
Ref:
Micro Switch
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Current
rating I
N
(A)
32
40
50
63
80
100
125
160
200
250
315
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
32
53
87
130
180
390
720
1550
2950
5560
11600
Total
Clearing
I
2
t @ U
N
(A
2
s)
170
280
470
700
970
2080
3890
8320
15900
29900
62300
Power
Losses
@ 0.8 In
9.5
10
10.5
11.5
12.5
15
18
22
27
33
40
Tested
Interrupting
rating
069NH0K0032F
069NH0K0040F
069NH0K0050F
069NH0K0063F
069NH0K0080F
0
690V
069NH0K0100F
069NH0K0125F
069NH0K0160F
069NH0K0200F
069NH0K0250F
069NH0K0315F
170kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V.
Micro switch reference : MS 4L 2-5B6
Size
Voltage
U
N
(V)
Ref:
069NH1K0063F
069NH1K0080F
069NH1K0100F
069NH1K0125F
Current
Micro Switch
rating I
N
(A)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
63
80
100
125
160
200
250
315
350
400
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
130
220
290
620
1170
2470
4670
9570
13400
19500
Total
Clearing
I
2
t @ U
N
(A
2
s)
700
1170
1570
3320
6270
13300
25100
51400
72300
105000
Power
Losses
@ 0.8 In
18
21,5
23
26
29
33
37
42
44
48
Tested
Interrupting
rating
1
690V
069NH1K0160F
069NH1K0200F
069NH1K0250F
069NH1K0315F
069NH1K0350F
069NH1K0400F
170kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V.
Micro switch reference : MS 4L 2-5B6
Data Sheet 069NHxKxxxxF Issue 1
Page 3 of 10
March, 2005
WESTCODE
An
IXYS Company
European Square Body Fuse – Knife Blade
Size
Voltage
U
N
(V)
Ref:
069NH2K0160F
069NH2K0200F
069NH2K0250F
069NH2K0315F
069NH2K0350F
Micro Switch
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Current
rating I
N
(A)
160
200
250
315
350
400
450
500
560
630
700
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
960
1710
3480
6860
9570
13400
21000
27400
38300
58700
78100
Total
Clearing
I
2
t @ U
N
(A
2
s)
5180
9220
18700
36900
51400
72300
113000
147000
206000
315000
420000
Power
Losses
@ 0.8 In
38
42
46.5
54
58
62.5
69
73
78
85
87
Tested
Interrupting
rating
2
690V
069NH2K0400F
069NH2K0450F
069NH2K0500F
069NH2K0550F
069NH2K0630F
069NH2K0700F
170kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V.
Micro switch reference : MS 4L 2-5B6
Size
Voltage
U
N
(V)
Ref:
069NH3K0315F
069NH3K0350F
069NH3K0400F
069NH3K0450F
069NH3K0500F
Current
Micro Switch
rating I
N
(A)
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
315
350
400
450
500
560
630
700
800
900
1000
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(A
2
s)
5251
7562
10500
15700
22200
30200
42000
61700
88900
123900
178400
Total
Clearing
I
2
t @ U
N
(A
2
s)
28200
40600
56500
84300
119000
163000
226000
332000
478000
666000
959000
Power
Losses
@ 0.8 In
57
58
65.5
70
75
80
89
100
112
125
140
Tested
Interrupting
rating
3
690V
069NH3K0550F
069NH3K0630F
069NH3K0700F
069NH3K0800F
069NH3K0900F
069NH3K1000F
170kA @ 690V
Notes: Minimum operating voltage for integrated trip indicator = 20V.
Micro switch reference : MS 4L 2-5B6
Data Sheet 069NHxKxxxxF Issue 1
Page 4 of 10
March, 2005
WESTCODE
An
IXYS Company
European Square Body Fuse – Knife Blade
Electrical Characteristics:
Times vs current characteristics
The following curves and those on page 6 indicate, for each rated current, pre-arcing time as a function
of RMS value of pre-arcing current I.
Tolerance for mean pre-arcing current:
±10% = ratings from (to be confirmed)
± 8% = ratings from (to be confirmed)
They do not show a minimum breaking capacity but limit currents of non-operation or operation in
compliance with standard VDE 636/23.
Data Sheet 069NHxKxxxxF Issue 1
Page 5 of 10
March, 2005
查看更多>
热门器件
热门资源推荐
器件捷径:
00 01 02 03 04 05 06 07 08 09 0A 0C 0F 0J 0L 0M 0R 0S 0T 0Z 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 1H 1K 1M 1N 1P 1S 1T 1V 1X 1Z 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 2G 2K 2M 2N 2P 2Q 2R 2S 2T 2W 2Z 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F 3G 3H 3J 3K 3L 3M 3N 3P 3R 3S 3T 3V 40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4M 4N 4P 4S 4T 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5E 5G 5H 5K 5M 5N 5P 5S 5T 5V 60 61 62 63 64 65 66 67 68 69 6A 6C 6E 6F 6M 6N 6P 6R 6S 6T 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7M 7N 7P 7Q 7V 7W 7X 80 81 82 83 84 85 86 87 88 89 8A 8D 8E 8L 8N 8P 8S 8T 8W 8Y 8Z 90 91 92 93 94 95 96 97 98 99 9A 9B 9C 9D 9F 9G 9H 9L 9S 9T 9W