V-EA-Series - UL508 Manual Motor Controller -
1 pole D-Trip
UL508 Listed
Minutes
E137938
Standard Pack:
12
Weight:
0.3A - 32A
1.68kg (3.7 lb.)
40A - 63A
1.92kg (4.23 lb.)
One Pole
35 mm
(1.38 in.)
91.5 mm
(3.60 in.)
70 mm
(2.76 in.)
17.5 mm
(0.69 in.)
For ring tongue terminal version, replace “U”
with “R” in part number. For example
1BR20
instead of
1BU20.
Tripping time t
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
12.5A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1DU03
1DU05
1DU075
NA
1DU1
1DU1.6
1DU2
1DU2.5
1DU3
1DU3.5
1DU4
1DU5
1DU6
1DU8
1DU10
NA
NA
1DU13
1DU15
1DU16
1DU20
1DU25
1DU30
1DU32
1DU40
1DU50
1DU60
1DU63
Approvals
UL
UL
UL
UL
UL
UL
V-EA-D Trip
0.3A Through 10A Rated Current
1.13-1.45xI
N
60
40
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
Tripping time t
UL
UL
UL
UL
UL
UL
UL
UL
UL
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8
10 16
20
40
100
UL
UL
UL
UL
UL
UL
UL
UL
UL
UL
Multiple of Rated Current
V-EA-D Trip
13A Through 63A Rated Current
1.13-1.45xI
N
60
40
Minutes
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
10
4
1
0.4
10
-1
4x10
-2
Voltage Rating
Seconds
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 12-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
Top: 18-3 AWG; Bottom: 18-2 AWG
20 lb.in.
IP20
10
-2
4x10
-3
10
-3
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
1
2
3 4 5 6 8
10 16
20
40
100
Multiple of Rated Current
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
all
all
all
all
*up to nearest rated current
Backup
Protection
Amp Range
0.3 - 10A
12 - 30/32A
40 - 50A
60 / 63A
UL-Listed
RK5-Fuse
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA