V-EA-Series - UL508 Manual Motor Controller -
1 pole E-Trip
UL508 Listed
E137938
Standard Pack:
12
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
Seconds
One Pole
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
74.7 mm
(2.94 in.)
17.5 mm
(0.69 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1E03UM
1E05UM
1E075UM
NA
1E1UM
1E1.6UM
1E2UM
1E2.5UM
1E3UM
1E3.5UM
1E4UM
1E5UM
1E6UM
1E8UM
1E10UM
1E12UM
1E13UM
1E15UM
1E16UM
1E20UM
1E25UM
1E30UM
1E32UM
1E40UM
1E50UM
1E60UM
1E63UM
Approvals
V-EA-E Trip
0.3A Through 10A Rated Current
1.05-1.35xI
N
60
40
Minutes
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
10
Tripping time t
4
1
0.4
10
-1
4x10
-2
10
-2
4x10
-3
10
-3
1
2
3 4 5 6 8 10
1418
20
40
100
Multiple of Rated Current
E0.3A-E10A
V-EA-E Trip
12A Through 60A Rated Current
1.05-1.35xI
N
60
40
Minutes
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
10
Tripping time t
4
1
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3
4 5 6
8
10 14 18
20
40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
all
all
all
all
Backup
Protection
Amp Range
0.3 - 10A
12 - 30/32A
40 - 50A
60 / 63A
UL-Listed
RK5-Fuse
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA
Ring
tongue
Box
clamp
*up to nearest rated current