T2S 160 TMD16-500 4p F F
General Information
Extended Product Type:
Product ID:
EAN:
Catalog Description:
Long Description:
T2S 160 TMD16-500 4p F F
1SDA051016R1
8015644514389
T2S 160 TMD16-500 4p F F
C.BREAKER TMAX T2S 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND
THERMOMAGNETIC RELEASE TMD R 16-500 A
Categories
Products
»
Low Voltage Products and Systems
»
Circuit Breakers
»
Moulded Case Circuit Breakers
»
Tmax T
Ordering
EAN:
Minimum Order Quantity:
Customs Tariff Number:
8015644514389
1 piece
85362090
Dimensions
Product Net Width:
Product Net Height:
Product Net Depth:
Product Net Weight:
120 mm
130 mm
70 mm
1.45 kg
Container Information
Package Level 1 Units:
Package Level 1 Width:
Package Level 1 Height:
Package Level 1 Length:
Package Level 1 Gross Weight:
Package Level 1 EAN:
1 piece
128 mm
135 mm
143 mm
1.55 kg
8015644514389
Environmental
RoHS Status:
Planned to follow EU Directive 2002/95/EC August 18, 2005 and amendment after 2006-07-
01
Additional Information
Electrical Durability:
IIT Publishing Status:
Mechanical Durability:
Number of Poles:
Power Loss:
Product Main Type:
Product Name:
Product Type:
Rated Current (I
n
):
Rated Impulse Withstand Voltage
(U
imp
):
Rated Insulation Voltage (U
i
):
Rated Operational Voltage:
Rated Service Short-Circuit
Breaking Capacity (I
cs
):
8000 cycle
120 cycles per hour
Level 0 - Information enabled
25000 cycle
240 cycles per hour
4
at Rated Operating Conditions per Pole 1,4 W
SACE Tmax T
Automatic Circuit Breaker
CB
16 A
8 kV
800 V
690 V AC
500 V DC
(220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 45 kA
(500 V AC) 30 kA
(690 V AC) 7 kA
(220 V AC) 8.5 kA
(230 V AC) 8.5 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
Rated Ultimate Short-Circuit
Breaking Capacity (I
cu
):
(440 V AC) 45 kA
(500 V AC) 30 kA
(690 V AC) 7 kA
(250 V DC) 2 Poles in Series 50 kA
(250 V DC) 3 Poles in Series 55 kA
(500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (I
u
):
160 A
Release Type:
TM
Standards:
IEC 60947
Sub-type:
T2
Suitable For:
T2
Suitable for Product Class:
Moulded Case Circuit Breakers
Terminal Connection Type:
Fixed Circuit-Breakers
Front
Test Voltage at Industrial Frequency
3000 V
for 1 Minute:
Test Voltage Max (U
test
):
3000 V
Version:
F
Certificates and Declarations (Document Number)
Data Sheet, Technical Information:
Data Sheet, Technical Information
(Part 2):
Declaration of Conformity - CE:
GL Certificate:
RoHS Information:
1SDC210004D0203
1SDM000030R0001
1SDL000165R0002
1SDL000163R0059
1SDL000200R0001
Classifications
Object Classification Code:
UNSPSC:
Q