International Products
British Dimension HRCII-C Fuses
600 Volts AC • 2– 600 Amperes
Specifications
Voltage Rating:
Interrupting Rating:
Ampere Range:
Approvals:
600 Volts AC, 250 Volts DC
200,000 amperes rms symmetrical AC
80,000 amperes rms symmetrical DC
2 – 600 amperes
CSA Certified to Standard C22.2 No. 106-M90
(File No. LR90341)
Ampere ratings
2CO
2
4
6
125
150
80
100
10
15
20
200
250
125
150
25
30
40
300
350
200
250
50
60
80
100
2CC
400
450
300
350
500
600
400
2CM
HRCII-C fuses are stud-mounted fuses designed to British standard
dimensions. They are generally used for motor short-circuit protection in
dead-front holders, and are normally required to be used in conjunction
with a motor running overload device.
Example part number (series & amperage): 2CM 150
Recommended Fuse Blocks
DF30 (F, B, FB) — Fits 2 – 30 amps
DF60 (F, B, FB) — Fits 40 – 60 amps
DF100 (F, B, FB) — Fits 80 – 100 amps
For additional information on HRCII-C fuse holders, contact factory.
D
G
A
B
J
E
J
G
K
E
D
G
A
H
F
B
FIG. 1
F
FIG. 2
FIG. 3
H
International Products
Cat. No.
2CO 2-30
2CO 40-60
2CO 80-100
2CC 125-200
2CC 250-400
2CC 450-600
2CM 80-100
2CM 125-200
2CM 250-400
Old LF
Part No.
FII
FII
FII
FIIC
FIIC
FIIC
FIIM
FIIM
FIIM
Refer To
Fig. No.
1
1
1
2
3
3
2
1
2
Dimensions in mm (inches in parentheses)
A
56 (2.2)
57 (2.24)
68 (2.88)
76 (3)
81 (3.19)
83 (3.27)
66 (2.6)
77 (3.03)
81 (3.19)
21
26
36
41
58
74
31
41
58
B
(0.83)
(1.02)
(1.42)
(1.61)
(2.28)
(2.91)
(1.22)
(1.81)
(2.25)
C
—
—
—
—
—
—
—
—
—
D
85 (3.3)
88 (3.45)
110 (4.33)
137 (5.39)
210 (8.27)
210 (8.27)
135 (5.31)
110 (4.33)
136 (5.35)
E
9 (0.35)
13 (0.51)
19 (0.75)
19 (0.75)
26 (1.02)
26 (1.02)
19 (0.75)
19 (0.75)
26 (1.02)
F
1 (0.04)
1.6 (0.06)
2.4 (0.09)
3.6 (0.14)
6.5 (0.26)
6.5 (0.25)
3.6 (0.14)
2.4 (0.09)
5.2 (0.2)
G
73 (2.87)
73 (2.87)
94 (3.7)
111 (4.37)
133 (5.24)
133 (5.24)
111 (4.37)
94 (3.7)
111 (4.37)
H
5.5 (0.21)
5.5 (0.21)
8.7 (0.34)
8.7 (0.34)
10.3 (0.4)
10.3 (0.4)
8.7 (0.34)
8.7 (0.34)
8.7 (0.34)
J
7.5 (0.29)
7.5 (0.29)
—
16 (0.63)
16 (0.63)
16 (0.63)
16 (0.63)
10.3 (0.4)
16 (0.63)
K
—
—
—
—
25.4 (1)
25.4 (1)
—
—
—
*Hole diameter to accept insulated stud (types C and D) mm min
© 2005 Littelfuse
•
POWR-GARD
™
Products Catalog
www.littelfuse.com
169