https://www.phoenixcontact.com/us/products/3072800
Disconnect terminal block - UK 6-T-P - 3072800
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Disconnect terminal block, Connection method: Screw connection, Cross section: 0.5 mm² -10 mm² , AWG: 20 -
10, Width: 8.2 mm, Mounting type: NS 35/7,5, NS 35/15, NS 32, Color: gray
Key Commercial Data
Packing unit
Minimum order quantity
Weight per Piece (excluding packing)
Custom tariff number
Country of origin
1 STK
50 STK
24.800 g
85369010
India
Technical data
Environmental Product Compliance
China RoHS
Hazardous substances above threshold values;
Environmentally Friendly Use Period = 50;
For details go to tab “Downloads”, Category “Manufacturer's declaration”
General
Number of levels
Number of connections
Nominal cross section
Color
Insulating material
Flammability rating according to UL 94
Rated surge voltage
Degree of pollution
Overvoltage category
1
2
6 mm²
gray
PA
V0
6 kV
3
III
09/08/2016 Page 1 / 20
https://www.phoenixcontact.com/us/products/3072800
Disconnect terminal block - UK 6-T-P - 3072800
Technical data
General
Insulating material group
Connection in acc. with standard
Nominal current I
N
Maximum load current
Nominal voltage U
N
Open side panel
Relative insulation material temperature index (Elec., UL 746 B)
Static insulating material application in cold
Behavior in fire for rail vehicles (DIN 5510-2)
Flame test method (DIN EN 60695-11-10)
Oxygen index (DIN EN ISO 4589-2)
NF F16-101, NF F10-102 Class I
NF F16-101, NF F10-102 Class F
Surface flammability NFPA 130 (ASTM E 162)
Specific optical density of smoke NFPA 130 (ASTM E 662)
Smoke gas toxicity NFPA 130 (SMP 800C)
Calorimetric heat release NFPA 130 (ASTM E 1354)
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
Fire protection for rail vehicles (DIN EN 45545-2) R26
I
IEC 60947-7-1
41 A
57 A (with 10 mm² conductor cross section)
500 V
Yes
130 °C
-60 °C
Test passed
V0
>32 %
2
2
passed
passed
passed
28 MJ/kg
HL 1 - HL 3
HL 1 - HL 3
HL 1 - HL 3
HL 1 - HL 3
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Dimensions
Width
Length
Height NS 35/7,5
Height NS 35/15
Height NS 32
8.2 mm
66.5 mm
48 mm
55.5 mm
53 mm
Connection data
Note
Conductor cross section solid min.
Conductor cross section solid max.
Conductor cross section flexible min.
Conductor cross section flexible max.
Conductor cross section AWG min.
Conductor cross section AWG max.
Terminal point
0.5 mm²
10 mm²
0.5 mm²
6 mm²
20
8
09/08/2016 Page 2 / 20
https://www.phoenixcontact.com/us/products/3072800
Disconnect terminal block - UK 6-T-P - 3072800
Technical data
Connection data
Conductor cross section flexible, with ferrule without plastic sleeve min.
Conductor cross section flexible, with ferrule without plastic sleeve max.
Conductor cross section flexible, with ferrule with plastic sleeve min.
Conductor cross section flexible, with ferrule with plastic sleeve max.
2 conductors with same cross section, solid min.
2 conductors with same cross section, solid max.
2 conductors with same cross section, stranded min.
2 conductors with same cross section, stranded max.
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, min.
2 conductors with same cross section, stranded, ferrules without plastic
sleeve, max.
0.5 mm²
6 mm²
0.5 mm²
6 mm²
0.5 mm²
2.5 mm²
0.5 mm²
4 mm²
0.5 mm²
2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic
0.5 mm²
sleeve, min.
2 conductors with same cross section, stranded, TWIN ferrules with plastic
4 mm²
sleeve, max.
Connection method
Stripping length
Internal cylindrical gage
Screw thread
Tightening torque, min
Tightening torque max
Screw connection
10 mm
A5
M4
1.5 Nm
1.6 Nm
Standards and Regulations
Connection in acc. with standard
Flammability rating according to UL 94
IEC 60947-7-1
V0
Drawings
Circuit diagram
Classifications
eCl@ss
eCl@ss 4.0
eCl@ss 4.1
eCl@ss 5.0
eCl@ss 5.1
27141126
27141126
27141126
27141126
09/08/2016 Page 3 / 20
https://www.phoenixcontact.com/us/products/3072800
Disconnect terminal block - UK 6-T-P - 3072800
Classifications
eCl@ss
eCl@ss 6.0
eCl@ss 7.0
eCl@ss 8.0
eCl@ss 9.0
27141126
27141126
27141126
27141126
ETIM
ETIM 2.0
ETIM 3.0
ETIM 4.0
ETIM 5.0
EC000902
EC000902
EC000902
EC000902
UNSPSC
UNSPSC 6.01
UNSPSC 7.0901
UNSPSC 11
UNSPSC 12.01
UNSPSC 13.2
30211811
39121410
39121410
39121410
39121410
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / EAC / EAC / cULus Recognized
Ex Approvals
Approval details
UL Recognized
mm²/AWG/kcmil
Nominal current IN
Nominal voltage UN
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B
26-8
30 A
600 V
C
26-8
30 A
600 V
09/08/2016 Page 4 / 20
https://www.phoenixcontact.com/us/products/3072800
Disconnect terminal block - UK 6-T-P - 3072800
Approvals
cUL Recognized
mm²/AWG/kcmil
Nominal current IN
Nominal voltage UN
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 60425
B
26-8
30 A
600 V
C
26-8
30 A
600 V
EAC EAC-Zulassung
EAC 7500651.22.01.00246
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
Cover profile
Cover profile - AP 3 CM - 5022876
Cover profile for covering terminal strips, snaps onto AP 3-TU, AP 3-TNS 35 cover profile carriers, can be labeled with
AP-ES insert strip. A cover profile carrier is to be positioned at the ends and at intervals of around approx. 40 cm. Supply
length: As per customer order
Cover profile - AP 3 METER - 5022643
Cover profile, for covering terminal strips, snaps onto cover profile carrier AP 3-TU, AP 3-TNS 35, can be marked with
insert strip AP-ES. Cover profile carriers should be placed at the ends and at intervals of approx. 40 cm. Length: 1 m
Cover profile carrier
09/08/2016 Page 5 / 20