Connectors for Copper Conductors
C o m p r e s s i o n
Cast Copper Two-Hole Lugs
for Code Copper Cable
Certified to 600V
and Recommended
up to 35 kV
¥
A
B
E
Bolt Size
C
D
H
F
Figure 1
E
C
Material:
Finish:
CAT. NO.
High-Conductivity
Cast Copper
Electro Tin Plate
Code Cable Size
Bolt G
Size (in.)
Dimensions in. (mm)
A
B
C
D
E
F
H
H
Figure 2
No. of Crimps
12 Ton
15 Ton
40 Ton
Die
Code
256-30695-1055
53204
53205
53206
53207
53208
53209
53210
53211
53212
53213
53214
53215
53216
53218
53220M
53222M
53223M
53269•
53224
53226
53228
53273•
53233
53233L
53432L•*
251-30485-1275
251-30485-1211
251-30485-1212
53239
#14-10
#8
#8
#4
#2
#1
1/0
2/0
3/0
4/0
250 kcmil
300 kcmil
350 kcmil
400 kcmil
500 kcmil
600 kcmil
700 kcmil
750 kcmil
1325/24
800 kcmil
900 kcmil
1000 kcmil
1100 kcmil
2750/24
1500 kcmil
1500 kcmil
1500 kcmil
1250 kcmil
1750 kcmil
1750 kcmil
2000 kcmil
169/110
178/0.104
2000 kcmil
169/0.110
178/0.104
2000 kcmil
1/4
1/4
1/4
1/4
1/4
1/4
3/8
3/8
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
9/16
–
–
1/2
2.00 (50.8)
2.00 (50.8)
2.00 (50.8)
2.00 (50.8)
3.00 (76.2)
3.00 (76.2)
3.00 (76.2)
4.31 (109.5)
4.31 (109.5)
4.31 (109.5)
4.56 (115.8)
4.56 (115.8)
5.31 (134.9)
5.31 (134.9)
5.31 (134.9)
5.31 (134.9)
5.31 (134.9)
5.31 (134.9)
5.50 (139.7)
6.00 (152.4)
6.00 (152.4)
6.00 (152.4)
6.19 (157.2)
6.25 (158.8)
7.31 (185.7)
7.31 (185.7)
6.19 (157.2)
6.38 (162.1)
6.38 (162.1)
6.19 (157.2)
1.31 (33.3)
1.31 (33.3)
1.31 (33.3)
1.31 (33.3)
2.00 (50.8)
2.00 (50.8)
2.00 (50.8)
3.00 (76.2)
3.00 (76.2)
3.00 (76.2)
3.00 (76.2)
3.00 (76.2)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.50 (88.9)
3.12 (79.2)
3.12 (79.2)
3.50 (88.9)
3.12 (79.2)
3.12 (79.2)
3.50 (88.9)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.75 (19.1)
0.75 (19.1)
0.75 (19.1)
0.75 (19.1)
1.00 (25.4)
1.00 (25.4)
1.18 (30.0)
1.18 (30.0)
1.38 (35.1)
1.38 (35.1)
1.38 (35.1)
1.63 (41.4)
1.63 (41.4)
1.63 (41.4)
1.63 (41.4)
1.88 (47.8)
1.88 (47.8)
1.88 (47.8)
2.12 (53.8)
2.25 (57.2)
2.00 (50.8)
3.00 (76.2)
2.12 (53.8)
3.00 (76.2)
2.25 (57.2)
2.75 (69.9)
0.12 (3.0)
0.09 (2.3)
0.12 (3.0)
0.12 (3.0)
0.12 (3.0)
0.25 (6.4)
0.25 (6.4)
0.18 (4.6)
0.28 (7.1)
0.28 (7.1)
0.18 (4.6)
0.31 (7.9)
0.25 (6.4)
0.38 (9.7)
0.38 (9.7)
0.53 (13.5)
0.03 (0.8) ±
0.03 (0.8) ±
0.40 (10.2)
0.31 (7.9)
0.46 (11.7)
0.46 (11.7)
0.56 (14.2)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.56 (14.2)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.38 (9.7)
0.38 (9.7)
0.38 (9.7)
0.38 (9.7)
0.59 (15.0)
0.59 (15.0)
0.59 (15.0)
0.84 (21.3)
0.84 (21.3)
0.84 (21.3)
0.93 (23.6)
0.93 (23.6)
1.21 (30.7)
1.21 (30.7)
1.21 (30.7)
1.35 (34.3)
1.35 (34.3)
1.35 (34.3)
1.35 (34.3)
1.56 (39.6)
1.56 (39.6)
1.56 (39.6)
1.90 (28.3)
1.90 (28.3)
1.88 (47.8)
1.88 (47.8)
1.90 (48.3)
2.18 (55.4)
2.18 (55.4)
2.18 (55.4)
0.25 (6.4)
0.25 (6.4)
0.25 (6.4)
0.25 (6.4)
0.50 (12.7)
0.50 (12.7)
0.50 (12.7)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
–
–
0.63 (16.0)
0.63–0.75
(16.0–19.1)
0.63 (16.0)
0.63 (16.0)
0.63 (16.0)
0.75 (19.1)
1.00 (25.4)
1.00 (25.4)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
1.75 (44.5)
–
–
0.63 (16.0)
29
29
29
29
45
45
45
66
66
66
76
76
99
99
99
112
112
112
107
130
130
130
150
or
150H
150
150
150
150
175
175
175
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
–
–
–
–
–
–
–
–
–
–
–
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
–
1
1
1
–
–
–
–
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
–
1
–
–
–
2 (fig. 2)
2 (fig. 1)
–
53239L
1/2
7.31 (185.7)
3.12 (79.2)
2.25 (57.2)
0.50 (12.7)
2.46 (62.5)
0.63 (16.0)
0.63 (16.0)
175
–
–
–
53439L•*
1/2
7.31 (185.7)
3.12 (79.2)
3.00 (76.2)
0.50 (12.7)
2.18 (55.4)
0.63 (16.0)
0.63 (16.0)
175
–
–
11421 Die
* Heavy Duty copper lugs for flexible strand cables 600V not UL or CSA Listed
• CSA not applicable
Die Selector Chart: pp.146–153
¥ For installations from 16 kV up to 35 kV, consult shielded cable manufacturers for stress relief and insulation requirements.
42