EMP Protection Units
Analog Communication and Control Lines
Series/Type:
B84320Z0010H033/B84320Z0010H035
Date: January 2004
©
EPCOS AG 2004. Reproduction, publication and dissemination of this data sheet, enclosures hereto and the
information contained therein without EPCOS' prior express consent is prohibited.
Purchase orders are subject to the General Conditions for the Supply of Products and Services of the Electrical
and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers' Associ-
ation), unless otherwise agreed.
EMP protection units
Analog communication and control lines
B84320Z0010H033
B84320Z0010H035
General
The EMP protection unit is sequenced, i.e. to use simultaneously the benefits of inert-gas-filled
surge arresters (extremely high surge capability) and of varistors (fast response). They are isola-
ted by a series inductor.
The arrester is housed in a plug-in socket, so it can be removed and tested without detaching the
lines.
Note on voltage figures:
The maximum voltage on the filter output depends primarily on the rise time until the arrester re-
sponds. For this reason the maximum voltage on the filter output is stated in the following table as
a function of the rising edge dv/dt of the pulse.
Technical data
Ordering code
Rated voltage V
R
Rated frequency f
R
Rated current I
R
Number of lines
Line impedance Z
L
Max. DC resistance R
max
Permissible ambient
temperature T
A
Climatic category
(EN 60068-1)
Approx. weight
Nominal DC spark-over
voltage V
sdcN
Nominal surge current
(8/20
µs)
Suppression condition
B84320Z0010H033
60
0 ... 10
1
10
600
<2
25/+40
25/085/56
300
<800
5
10
I < I
R
g
V
kA
kA
Ω
Ω
°C
V
A
B84320Z0010H035
140
1
10
600
<2
25/+40
25/085/56
300
<800
5
10
I < I
R
g
V
kA
kA
Line/line
Pair/case
Ω
Ω
°C
25
°C/+85 °C/56
days
damp heat test
Per line
V
kHz Pass bandwidth at Z
L
A
T
A
= 40
°C
Pairs
kHz 0 ... 10
Maximum voltage on filter output:
At rising edge
dv/dt = 0.1 kV/µs
dv/dt = 1 kV/µs
dv/dt = 1 kV/ns
1)
Unsymmetrical
≤190
V
≤260
V
≤16
V
Unsymmetrical
≤200
V
≤180
V
≤20
V
Symmetrical
≤17
V
≤15
V
≤8
V
1) Typical test pulse: rise time 10 ns, time to half value 1500 ns, charge voltage min. 50 kV, source impedance 90
Ω
2
EMP protection units
Analog communication and control lines
B84320Z0010H033
B84320Z0010H035
Circuit diagram
(only one of 10 pairs shown)
Insertion loss
α
e
per pair
(typical values at Z = 50
Ω)
Asymmetrical measurement circuit
to MIL-STD-220A
3
EMP protection units
Analog communication and control lines
B84320Z0010H033
B84320Z0010H035
Dimensional drawing
Side view
Terminal strip:
Terminals with cage strain system, suitable for
conductors 0.08 ... 2.5 mm
2
Front view of protected end
Installation section and attachment
4