CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
General Information:
• GMQ fuse mounts in type HLQ size rejection (size limiting)
carrier (prevents overfusing).
• HLQ carrier comes with 6” of #18 red insulated solid cop-
per wire attached to the line side.
• Customer inserts a #18 insulated solid copper wire into
load side receptacle.
• Size of type GMQ fuses varies with ampere ratings.
• Fuse and knob are an integral one-piece unit. There are no
replacement knobs (caps).
• Units can be panel mounted with a separate steel clip. For
the knockout hole (see above), choose #BK/A-104. For the
keyhole punch type hole, choose #6374 for panels .043” to
.062” thick, or #4909 for panels .030” to .042” thick.
• Do not put tension on line (rear) termianl of fuleholder.
5-22-02
SB02233
Form No. GMQ & HLQ
Page 1 of 2
Data Sheet: 2030
Bussmann
®
Specialty Fuse
Time-Delay, Rejection Style
Time-Current Characteristic Curves–Average Melt
3
3.2
4
100
GMQ
& HLQ
Time-Current Characteristic Curves–Average Melt
100
AMPERE
RATING
AMPERE
RATING
.2
1
1.6
2
.3
.5
10
10
TIME IN SECONDS
TIME IN SECONDS
1
1
.1
.1
100
100
200
CURRENT IN AMPERES
CURRENT IN AMPERES
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This
bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without
notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any
technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.