Data Sheet
August 2009
Compact Power Line
CP2000AC54 Front-End Power Supply
Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
Features
•
Compact 1-RU form factor providing 20 W/in3
•
Constant power from 52 – 58 Vdc
•
2000W from nominal 200 – 240 Vac
•
1200W from nominal 100 – 120 Vac
•
Output voltage programmable from 44V – 58 Vdc;
•
•
Applications
•
48Vdc distributed power architectures
•
Power over Ethernet
•
Routers/Switches
•
VoIP/Soft Switches
•
LAN/WAN/MAN applications
•
File servers
•
Indoor wireless
•
Telecommunications equipment
•
Enterprise Networks
•
SAN/NAS/iSCSI applications
•
Advanced workstations
•
•
•
•
•
•
•
•
•
•
•
output defaulted to 54V
PMBus compliant dual I
2
C and RS485 serial bus
communications
Power factor correction (meets EN/IEC 61000-3-2
and EN 60555-2 requirements)
Tested to IEEE802.3 Compliance, 2250 output***
isolation to chassis/signals for POE applications.
(see ordering info)
DC Output over-voltage and over-current
protection
AC Input over-voltage and under-voltage protection
Over-temperature warning and protection
Redundant, parallel operation with active load
sharing and redundant +5V Aux power
Remote ON/OFF
Hot insertion/removal (hot plug)
Four front panel LED indicators
UL* Recognized to UL60950-1, CAN/ CSA
†
C22.2
No. 60950-1, and VDE
‡
0805-1 Licensed to
IEC60950-1
CE mark meets 2006/95/EC directive
§
Internal variable-speed fan control
The CP2000AC54 Front-End Power Supplies
in the Compact Power Line platform are specifically
designed to operate as an integral part of a complete distributed power system. The high-density, front-to-
back airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. It
is provided with many features including PoE isolation, RS485 and dual-redundant I
2
C communications
busses that allow it to be used in a broad range of applications. The flexible feature set makes this front-
end power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate
voltages, such as in distributed power.
UL is a registered trademark of Underwriters Laboratories, Inc.
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user
equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
*** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3.
*
†
‡
§
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications
Input
Parameter
Startup Input Voltage
1200W Operation
2000W Operation
Operating Voltage Range
1200W Configuration
2000W Configuration
2000W Configuration
Permitted Excursions
Surges
Input Frequency
Input Current
85
175
150
275
300
47
13.3
11.2
11.8
9.9
25
1.5
0.98
85
88
90
93
%
35
120/200/240
200/240
Min
Typ
Max
85
175
275
275
175
300
325
63
Hz
A
At 100 Vac
At 120 Vac
At 200 Vac
At 240 Vac
Measured at 25°C for all line conditions; does
not include X-Capacitors charging.
Measured at 265Vac, 60Hz
From 50% to 100% load.
At 100 Vac with Vout > 52V and Pout > 50%.
At 230 Vac with Vout > 52V and Pout > 50%.
Measurement starts at zero crossing of the ac
voltage. Alarm issued via PFW signal going LO
5 ms prior to output voltages going out of limits.
Measurements made at 65% full load and
voltage allowed to decay to 49.5V.
Units
Notes
The power supply automatically configures its
operating mode based on the voltage level it
reads on first turn ON. (This information is
retained as long as internal bias is maintained.)
Vac
If started within low input line range.
If started within high input line range.
Will derate to 80% of full load; will shutdown
below 150Vac.
May not meet all requirements, but will
maintain output regulation.
May shut down but will not get damaged.
Inrush Transient
Input Leakage Current
Power Factor
Efficiency
Apk
mA
Holdup Time
15
ms
20
Main Output
Parameter
Maximum Output Power
Output Voltage Setpoint
Setpoint Accuracy
Overall Regulation
Output Voltage Margin
Maximum Output Current
Current Share
-1
-2
44
42
54
+1
+2
58
58
23
38.5
10
Min
Typ
Max
1200
2000
Units
W
Vdc
%
%
Vdc
Vdc
A
%FL
For loads below 1200W.
Notes
At low-line input from 100-120Vac nominal.
At high-line input from 200-240Vac nominal.
Output floats with respect to frame ground.
Includes all variations due to specified load
range, drift, and environmental conditions.
Configured by hardware setting.
2
Set either by I C or RS485
At 1200W, 52V and 100-120Vac.
At 2000W, 52V and 200-240Vac.
Maintains tolerance to the average of all other
rectifiers. Loads > 25%FL
Lineage Power
2
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Output (continued)
Parameter
Output Ripple
RMS (5Hz to 20MHz)
Peak-to-Peak (5Hz to 20MHz)
Psophometric Noise
External Bulk Load Capacitance
0
Turn-On
Delay
1
Rise Time - Standard (PMBus)
2
-Telecom (RS-485)
Overshoot
Load Step Response
∆I
∆V
Response Time
Overload
Power Limit
3
Current Limit Inception
Over-voltage
Delayed
Immediate
Latchoff
Over-temperature
Warning
Shutdown
Auto-recoverable
20
2000
102
5,000
Min
Typ
Max
250
500
2
Units
mVrms
mVpk-pk
mVrms
µF
Notes
Measured with 20MHz bandwidth under any
condition of loading. Minimum load is 1A.
External capacitance can be increased but the
power supply will not meet its turn-ON rise time
requirement.
Monotonic Turn_On from 30% to 100% of Vnom
above -5°C operation. Monotonic Turn_On from
60% to 100% of Vnom below -5°C operation.
5
100
5
2
50
2.0
2
s
ms
s
%
%FL
Vdc
ms
W
%FL
Vdc
Vdc
∆I/∆t
slew rate 1A/µs.
Settling time to within regulation requirements.
108
60
65
Down to -52Vdc
Hiccup current limit. (FL = 38.5A)
200msec delayed shutdown to be implemented.
Instantaneous shutdown above this point.
Three restart attempts may be implemented within a one minute window prior to a latched
shutdown
5
°C
°C
Implemented prior to commencement of an OT
shutdown
Below the maximum rating of the device being
protected
Temperature hysteresis of approximately 10°C provided between shutdown and restart.
1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.
2. Complies with GR947 which calls for a minimum rise time proportional to output load.
3. Fold-down current limit is programmed as a default to permit system start-up when units are plugged in one at a time. Latch-
off mode current limit can be activated via an I2c command.
Auxiliary Output
Parameter
Output Voltage Setpoint
Output Current
Overall Regulation
Ripple and Noise
Over-voltage Clamp
Over-current Limit
110
0.005
-5
50
Min
Typ
5
0.75
+10
100
7
175
Max
Units
Vdc
A
%
mVpk-pk
Vdc
%FL
20MHz bandwidth
Notes
Physical
Length (in./mm)
Width (in./mm)
Height (in./mm)
Weight (lb/kg)
13.85 / 351.8
4.00 / 101.6
1.66 / 42.2
4.6 / 2.1
Lineage Power
3
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Environmental
Parameter
Ambient Temperature
Operating
Ambient Derating
2
Power Derating
Storage Temperature
Humidity
Shock and Vibration
Operational Test
Test Levels
Drop and Tip Over
Earthquake Rating
Acoustic Noise
Harmonic Emissions
Radiated Emissions
4
Min
-5
1
Typ
Max
45
Units
°C
°C
%/°C
%/°C
°C
%
Notes
Air inlet from sea level to 5,000 feet.
Per 1,000 feet above 5,000 feet.
Up to 55°C
From 55 to 75 °C
Relative humidity, non-condensing
IEC 68-2
IEC 721-3-2
IEC 68-2-31
1
1
2
-40
5
85
95
4
45
Per EN/IEC61000-3-2
dBA
Zone
Per Telcordia GR-63-CORE, all floors, when
installed in CP Shelf.
Noise is proportional to fan speed, load and
ambient temperature.
FCC and CISPR22 (EN55022) - Class B
FCC and CISPR22 (EN55022) Class B
Telcordia GR-1089-CORE - Class A
3
Conducted Emissions - ac
Conducted Emissions - dc
ESD
Radiated Immunity
Electrical Fast Transient Burst
Lightning Surge
Error Free
Damage Free
Conducted Immunity
Reliability (calculated)
Isolation
Input-Chassis/Signals
Input - Output
Output-Chassis/Signals
Service Life
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).
ANSI C62.41 Level A3 (6 kV common and differential mode)
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
400,000
Hours
At ambient of 25°C at full load per Telcordia SR-
332, Reliability Prediction for Electronic Equipment,
Method I Case III.
Per EN60950-1.
Consult factory for testing to this requirement
Per IEEE802.3.
25°C ambient, full load excluding fans.
1500
3000
2250
10
Vrms
Vrms
Vdc
Years
1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.
2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate
faster if the input line is below nominal.
3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the
cable. See the figure below.
4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode
capacitors that assist in meeting compliance.
Lineage Power
4
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Status and Control
The rectifier provides three means for
monitor/control: analog, PMBus compliant I
2
C, or
RS485 for interfacing to Lineage Power controllers
or battery plants.
Details of analog controls are provided in this data
sheet under Signal Definitions. Lineage Power will
provide separate application notes on PMBus
protocol for users to interface to the CPL rectifiers.
Contact your local Lineage Power representative
for details.
Module Present Signal:
This signal has dual
functionality. It can be used to alert the system
when a module is inserted. Has a 500Ω resistor in
series between this signal and Logic GRD. An
external pull-up should not raise the voltage on the
pin above 0.25Vdc. If raised the pin is raised to
5Vdc the write_protect feature of the EEPROM is
enabled.
Protocol Select:
Establishes the communications
mode of the power supply, between analog/I
2
C and
RS485 modes. For RS485, connect 750 – 3.92kΩ
pull-down resistor to 54_OUT(-DC).
Enable:
On/Off control when either PMBus
communications or analog functions are utilized as
configured by the Protocol pin. This pin must be
pulled low to turn
ON
the main output of the power
supply. The power supply will turn
OFF
if either the
Enable
or the
ON/OFF
pin is released. The
Enable
function does not work with the RS-485 protocol.
This signal is referenced to Logic_GRD.
ON/OFF:
This is a short pin utilized for hot-plug
applications to ensure that the power supply turns
OFF
before the power pins are disengaged. It also
ensures that the power supply turns
ON
only after
the power pins have been engaged. Must be
connected to 54_OUT (-DC).
Hot Plug
When rapidly extracting and reinserting modules
care should be taken to allow for discharging the
internal bias supply so that a predictable restart
could be achieved. The way to ensure that the
circuit sufficiently discharges is to observe the
spinning of the fans after an extraction. The unit
should not be reinserted until the fans stop
spinning.
Control Definitions
All signals are referenced to Logic GRD unless
otherwise noted. See the Signal Definitions Table
at the end of this document for further description
of all the signals.
Input Signals
Margining:
Setpoint of the rectifier can be changed
via this input pin. Programming can be either a
voltage source or a resistance divider. The
margining pin is connected to 3.3Vdc via a 10kΩ
resistor inside the rectifier. See graphs below.
Output Signals
Alert #:
PMBus interrupt signal.
Fault:
This signal goes LO for any failure that
requires rectifier replacement. Some of these faults
may be due to:
•
Fan failure
•
Over-temperature condition
•
Over-temperature shutdown
•
Over-voltage shutdown
•
Internal Rectifier Fault
Power Capacity:
A HI on this pin indicates rectifier
configured for 2000W operation; a LO indicates
rectifier configured for 1200W operation.
An open circuit on this pin reverts the voltage level
back to the original setting.
Lineage Power
5