首页 > 器件类别 > 模拟混合信号IC > 过滤器

FN3441-160-118-E0FXSXX

Three Phase EMI Filter,

器件类别:模拟混合信号IC    过滤器   

厂商名称:Schaffner

器件标准:

下载文档
器件参数
参数名称
属性值
是否Rohs认证
符合
厂商名称
Schaffner
Reach Compliance Code
compliant
文档预览
DATASHEET
Evo line (5% THID) FN 3441
Ecosine evo, 50 Hz Passive Harmonic Filters
The industry standard for 6-pulse rectifier and
motor drives
Filters for diode rectifier with DC-link choke
Best-in-class partial load performance
Most compact design
Plug and play, ready to use
Approvals
(depending on filter configuration)
Features and benefits
Schaffner ecosine harmonic filters represent an
economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
virtually any kind of power electronics with front-end
six-pulse rectifiers, 3-phase diode or thyristor bridges,
where harmonic current distortion needs to be
reduced to defined limits.
Technical specifications
Nominal operating voltage
Operating frequency
Nominal motor drive input power rating
Total harmonic current distortion THID*
Efficiency
High potential test voltage
Protection category
Cooling
Overload capability
Ambient temperature range
3 x 380 VAC to 415 VAC ±10%
50 Hz ±1 Hz
1.1 to 200 kW
≤5% at rated power
>98% for rated voltage and power
P –> E 2160 VAC (1 s)
IP 00, IP 20
Internal fan cooling or external cooling**
1.6x rated current for 1 minute, once per hour
–25°C to +45°C fully operational
–25°C to +85°C transport and storage
+45°C to +70°C derated operation***
UL 94 V-2
Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6
>200,000 hours
100 kA
TN, TT, IT
OV III (IEC 60664-1 / UL 61800-5-1)
Typical applications
Equipment with front-end six-pulse rectifier
Motor drives
Factory automation equipment
Water/wastewater treatment facilities
Fan and pump applications
HVAC installations
Mission-critical processes
DC fast chargers
Flammability corresponding to
Design corresponding to
MTBF @ 45°C/415 V (Mil-HB-217F)
SCCR****
Earthing System
Overvoltage category
Typical electrical schematic
***
*System
requirements: THVD <2%, line voltage unbalance <1%
****
Note: performance specifications in this brochure refer to six-pulse diode rectifiers with 8% DC-link choke.
THID ~5% at rated power for filter <6 kW
***
*Please
check the inlet air flow required for cooling table on page 6 of this document.
**** I
derated
= I
nominal
*√((T
max-
T
amb
)/(T
max-
T
nominal
)) = I
nom
*√((70°C-T
amb
)/25°C)
**** External UL-rated fuses required. Please consult the user manual.
(all configurable optional fuctionalities shown)
2
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Filter selection table – IP 00 enclosure
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN 3441-1-110-E0_ _ _ _ _*
FN 3441-2-110-E0_ _ _ _ _*
FN 3441-4-112-E0_ _ _ _ _*
FN 3441-6-112-E0_ _ _ _ _*
FN 3441-8-112-E0_ _ _ _ _*
FN 3441-11-113-E0_ _ _ _ _
FN 3441-15-113-E0_ _ _ _ _
FN 3441-19-113-E0_ _ _ _ _
FN 3441-22-115-E0_ _ _ _ _
FN 3441-30-115-E0_ _ _ _ _
FN 3441-37-115-E0_ _ _ _ _
FN 3441-45-115-E0_ _ _ _ _
FN 3441-55-115-E0_ _ _ _ _
FN 3441-75-116-E0_ _ _ _ _
FN 3441-90-116-E0_ _ _ _ _
FN 3441-110-118-E0_ _ _ _ _
FN 3441-132-118-E0_ _ _ _ _**
FN 3441-160-118-E0_ _ _ _ _**
FN 3441-200-118-E0_ _ _ _ _**
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
Motor drive
input current***
[Arms]
1.7
3.4
6.2
8.5
12
17
23
29.3
34
46
57
70
85
116
140
171
205
249
312
Rated filter
input current
[Arms]
1.62
3.23
5.9
8.1
11
16
22
28
32
44
54
66
81
110
133
162
195
238
297
Min. required
L
DC
****
[mH]
37.41
18.71
10.29
7.483
5.487
3.741
2.744
2.166
1.871
1.372
1.112
0.915
0.748
0.549
0.457
0.374
0.312
0.257
0.206
Min. required
L
AC
****
[mH]
9.8
6.01
3.48
2.548
1.818
1.264
0.909
0.724
0.637
0.454
0.361
0.297
0.245
0.178
0.147
0.12
0.099
0.085
0.064
[kg]
6
9
12
15
16
23
26
30
38
43
48
54
63
98
106
127
149
167
209
110
110
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
C
C
D
D
D
E
E
E
E
E
G
G
H
H
H
H
Weight
Terminal
Frame size
*
Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** In order to apply FN 3441 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3441 filter must not be used. In this case, FN 3440 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
4
8
8
14
14
25
25
25
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
3
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Filter selection table - IP 20 enclosure
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN 3441-1-110-E2_ _ _ _ _*
FN 3441-2-110-E2_ _ _ _ _*
FN 3441-4-112-E2_ _ _ _ _*
FN 3441-6-112-E2_ _ _ _ _*
FN 3441-8-112-E2_ _ _ _ _*
FN 3441-11-113-E2_ _ _ _ _
FN 3441-15-113-E2_ _ _ _ _
FN 3441-19-113-E2_ _ _ _ _
FN 3441-22-115-E2_ _ _ _ _
FN 3441-30-115-E2_ _ _ _ _
FN 3441-37-115-E2_ _ _ _ _
FN 3441-45-115-E2_ _ _ _ _
FN 3441-55-115-E2_ _ _ _ _
FN 3441-75-116-E2_ _ _ _ _
FN 3441-90-116-E2_ _ _ _ _
FN 3441-110-118-E2_ _ _ _ _
FN 3441-132-118-E2_ _ _ _ _**
FN 3441-160-118-E2_ _ _ _ _**
FN 3441-200-118-E2_ _ _ _ _**
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
Motor drive
input current
[Arms]***
1.7
3.4
6.2
8.5
12
17
23
29.3
34
46
57
70
85
116
140
171
205
249
312
Rated filter
input current
[Arms]
1.62
3.23
5.9
8.1
11
16
22
28
32
44
54
66
81
110
133
162
195
238
297
Min. required
L
DC
****
[mH]
37.41
18.71
10.29
7.483
5.487
3.741
2.744
2.166
1.871
1.372
1.112
0.915
0.748
0.549
0.457
0.374
0.312
0.257
0.206
Min. required
L
AC
****
[mH]
9.8
6.01
3.48
2.548
1.818
1.264
0.909
0.724
0.637
0.454
0.361
0.297
0.245
0.178
0.147
0.12
0.099
0.085
0.064
[kg]
7
9
13
16
18
27
30
34
44
48
54
59
68
107
115
144
166
185
226
110
110
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
C
C
D
D
D
E
E
E
E
E
G
G
H
H
H
H
Weight
Terminal
Frame size
*
Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** In order to apply FN 3441 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3441 filter must not be used. In this case, FN 3440 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
4
8
8
14
14
25
25
25
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
4
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Product selector
Table 1: Filter configurations if external air flow is available for cooling
(Filters do
not contain fan
and do
not contain aux. power supply)
E0XXXXX
- For rectifiers with DC-link choke
E0XXJXX
- For rectifiers with DC-link choke
- Filters contain trap disconnect
jumper
E0XXXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module
E0XXJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module and trap disconnect
jumper
5
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Table 2: Filter configurations with embedded ventilation
(Filters
contain fan
and
aux. power supply)
E0FAXXX and E2FAXXX
- For rectifiers with DC-link choke
- Filters contain fan and aux. power
supply
E0FAJXX and E2FAJXX
- For rectifiers with DC-link choke
- Filters contain fan, aux. power
supply and trap disconnect
jumper
E0FAXRX and E2FAXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply and RC damper module
E0FAJRX and E2FAJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply, RC damper module and
trap disconnect jumper
Table 3: Filter configurations if external aux. power supply for the fan is available
(Filters
contain fan
but do
not contain aux. power supply,
user should provide aux. power supply to the fan)
E0FXXXX and E2FXXXX
- For rectifiers with DC-link choke
- Filters contain fan
E0FXJXX and E2FXJXX
- For rectifiers with DC-link choke
- Filters contain fan and trap
disconnect jumper
E0FXXRX and E2FXXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan and RC
damper module
E0FXJRX and E2FXJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, RC damper
module and trap disconnect
jumper
查看更多>
热门器件
热门资源推荐
器件捷径:
E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 EA EB EC ED EE EF EG EH EI EJ EK EL EM EN EO EP EQ ER ES ET EU EV EW EX EY EZ F0 F1 F2 F3 F4 F5 F6 F7 F8 F9 FA FB FC FD FE FF FG FH FI FJ FK FL FM FN FO FP FQ FR FS FT FU FV FW FX FY FZ G0 G1 G2 G3 G4 G5 G6 G7 G8 G9 GA GB GC GD GE GF GG GH GI GJ GK GL GM GN GO GP GQ GR GS GT GU GV GW GX GZ H0 H1 H2 H3 H4 H5 H6 H7 H8 HA HB HC HD HE HF HG HH HI HJ HK HL HM HN HO HP HQ HR HS HT HU HV HW HX HY HZ I1 I2 I3 I4 I5 I6 I7 IA IB IC ID IE IF IG IH II IK IL IM IN IO IP IQ IR IS IT IU IV IW IX J0 J1 J2 J6 J7 JA JB JC JD JE JF JG JH JJ JK JL JM JN JP JQ JR JS JT JV JW JX JZ K0 K1 K2 K3 K4 K5 K6 K7 K8 K9 KA KB KC KD KE KF KG KH KI KJ KK KL KM KN KO KP KQ KR KS KT KU KV KW KX KY KZ
需要登录后才可以下载。
登录取消