RP
RP220 Series
RP220
DUAL STAGE TO 20A
CHASSIS MOUNT FILTER
ROHS COMPLIANT
RADIUS POWER
Your Power Partner
High Performance Dual Stage Power Line Filter
SPECIFICATIONS
Operating Freq.
Usable Freq.
Max. Operating Voltage
Ambient Temperature
Climatic Category
Hipot Rating (L-G)
Terminals (-T)
Safety Approvals
Typ. Weight, LBS (KG)
:
:
:
:
:
:
:
:
:
50/60Hz
DC - 400Hz
250V +10%
-25 to 40C
25/100/21
2700VDC
QD: 0.25 Tabs
cURus, EN60939
0.8 (0.4)
LEAKAGE CURRENT
Y-cap, nF
0
.47
1
2.2
4.7
10
mA,
120V/60Hz
0
0.04
0.09
0.2
0.4
0.9
mA,
250V/60Hz
0
0.08
0.18
0.4
0.8
1.8
PART NUMBER/ ORDERING
RP220
-X
(Amps)
6
10
12
16
20
-Y
(Ycap, nF)
0
.47
1
2.2
4.7
10
Note:
Use any combination of -Y with any -X (Amps) rating
e.g. RP220-10-10-QD (10Amps with 10nF Ycap)
SCHEMATIC
-T
QD
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
24
RP
RP220
Typical Insertion Loss, dB (50/50ohm)
6 Amp
FREQ (MHz)
CM(dB)
DM(dB)
.15
60
50
.5
70
60
1.0
70
68
10
52
60
30
50
60
RADIUS POWER
Your Power Partner
Mechanical Dimensions
10 Amp
FREQ (MHz)
CM(dB)
DM(dB)
.15
55
45
.5
70
60
1.0
70
60
10
50
70
30
50
65
12 Amp
FREQ (MHz)
CM(dB)
DM(dB)
.15
56
45
.5
70
60
1.0
70
68
10
50
60
30
50
60
16 Amp
FREQ (MHz)
CM(dB)
DM(dB)
.15
42
36
.5
65
60
1.0
70
65
10
55
65
30
50
60
TYPICAL TOLERANCE: +/-0.02 (0.50)
20 Amp
FREQ (MHz)
CM(dB)
DM(dB)
.15
40
34
.5
65
58
1.0
70
60
10
52
65
30
40
60
www.radiuspower.com
Reference purposes only.
Specifications are subject to change.
Consult factory to verify specifications.
Engineering Assistance: engg@radiuspower.com
Sales:sales@radiuspower.com
25