Description (Continued)
General Notes:
•
Strobes are designed to flash at one flash per second
minimum over the Regulated Voltage Range. Note that
NFPA-72 (1999) specifies a flash rate of one to two
flashes per second and ADA guidelines specify a flash
rate of one to three flashes per second.
•
All candela ratings represent minimum effective strobe
intensity based on UL Standard 1971.
•
Series AS strobe products are Listed under UL Standard
1971 for indoor use with a temperature range of 32° F to
120° F (0° C to 49° C) and a maximum humidity of 93%
(+/- 2%).
•
Series AH horns are Listed under UL Standard 464 for
audible signal appliances (indoor use only).
•
Series AH-24WP audible appliances are Listed under UL
Standard 464 for indoor/outdoor use with a temperature
range of –31° F to 150° F
(-35° C to 66° C) and a maximum humidity of 95%.
•
“Regulated Voltage Range” is the state-of-the-art technol-
ogy used by UL to identify the voltage range. Prior to this
technology, UL used the term, “Listed Voltage Range.”
Table 3: Average Mean Current * Series
AH-24R/W & AH-12-R/W * W P (Horn only)
Voltage
High
Medium
16.0 VDC
0.035
0.020
24.0 VDC
0.050
0.026
33.0 VDC
0.089
0.035
8.0 VDC
0.093
0.037
12.0 VDC
0.108
0.049
17.5 VDC
0.128
0.069
Low
0.14
0.017
0.021
0.080
0.085
0.042
Table 4: Avereage RM* Current Series AS0241575
Voltage
16.0 VDC
24.0 VDC
33.0 VDC
High
0.130
0.107
0.105
Medium
0.114
0.085
0.075
Low
0.108
0.075
0.060
Table 5:dBA Ratings for 12 VDC & 24 VDC Series
AS/AH 12 & 24 VDC Horns
Reverberant dBA
per UL 464 @
Description Volumn 10 pt.
Continuous
High
91
Horn
Medium
88
Low
83
Temporal
High
87
Pattern
Medium
84
Low
79
Anchoic
dBA @
10 pt.
99
95
90
99
95
90
Table 1: Ratings per UL 1971
Input
Voltage
VDC
Model
AS-24MCW-FA 24
AS-241575W-FR 24
AS-121575W-FR 12
AS-24M C C –FW
24
AS WP-2475W-FR
24
Regulated Voltage
Range VDC/FW R
160-330
160-330
80-175
160-330
160-330
Strobe
Candela (cd)
15/30/75/110
15 (75 or Axis)
15 (75 or Axis)
15/30 /75 /95
75 @ -31° F
Table 2: Average RMS Current* fir AS-24 MCW Wall-
Models @ each Candela Setting
Average Current with High dBA Setting (99 dBA)
Voltage
15 cd
30 cd
75 cd
110 cd
16.0 VDC 0.099
0.135
0.219
0.308
24.0 VDC 0.093
0.114
0.157
0.197
33.0 VDC 0.098
0.108
0.138
0.166
Average Current with Medium dBA Setting (95 dBA)
16.0 VDC 0.078
0.116
0.203
0.282
24.0 VDC 0.065
0.088
0.133
0.179
33.0 VDC 0.065
0.078
0.106
0.134
Average Current with Low dBA Setting (90dBA)
16.0 VDC 0.070
0.111
0.201
0.279
24.0 VDC 0.052
0.077
0.126
0.169
33.0 VDC 0.046
0.063
0.063
0.121
Table 6: Average RM S Current* for AS-24 M CC Ceil-