680-1200 Watts
BML 231 002 /204
680 watt -48 VDC rectifier
Electrical Specs - 002
Input
AC Input voltage
Frequency
Efficiency
Power factor
220-240 VAC (176-288 VAC)
50/60 Hz (± 10%)
>90% @ ≥60% load
>0.95 @ ≥50% load
Output
DC output voltage
Maximum output power
-54.0 V @10A load (-45 to -58.5 VDC)
680W @ -45 to -58.5 VDC
Automatic shut-down before -60VDC
> 10ms
Special Features - 002
•
•
•
•
•
•
•
•
•
•
•
680 W constant power output
High efficiency
PFC
Hot-swappable
Passive load sharing
Front access
Soft start
Over load and over voltage protection
Designed for ETSI mechanical structure
Controls for remote shut-down
size: 2.9” W x 10.4” H x 8.8 “ D
Weight: 4.3 kg (9.5 lbs)
Over voltage protection
Hold-up time
Electrical Specs - 204
Input
AC input voltage range
Frequency
Efficiency
Power factor
100-250 VAC (90-275 VAC)
50 / 60 Hz (45-65 Hz)
> 90% 230 VAC @ ≥50% load
>0.95 230 VAC @ ≥50% load
Special Features - 204
• 1200 W Constant Power Output
• High efficiency
• High power density
• PFC
• Front access
• Soft start
• Analog or opto interface
• Universal input
• Forced convection cooling
• Compact dimensions
Front: 10.3” x 2.4”
Body: 9.2”H x 2.9”W x 8.8”D
weight: 3.5 kg (7.7 lbs)
Output
DC output voltage
Maximum output power
Dynamic regulation
Hold-up time
-54.5 (-44.0 to -58.5 VDC)
1200 W @ 180-275 VDC
1000 W @ 90-140 VDC
±5% of output voltage
>20ms
Ordering Information
BML231002/3
BML231204/1
BML231204/2
680 W -48VDC rectifier
1200 W rectifier with opto interface
1200 W rectifier with analog interface
180
America’s (USA): 1-888-41-ASTEC
Europe (UK): 44 (1384) 842-211
Asia (HK): 852-2437-9662
rev 12.01.01
AMERICAS
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
EUROPE
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
ASIA
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
BML 231 002 / 204
Environmental & Safety
BML231 002
Temperature: +5°C to +45°C (normal operation)
CE: EMC Directive 89/336/EEC & 92/31/EEC and Low
Voltage Directive 73/23/EEC
EMC:
EN 50 081-1
EN 50 082-1
EN 55 022, class B
EN 61000-4-2,3,4,5,6
EN 60950
IEC 950/EN 60950
UL 1950
CAN/CSA C22.2
BML 231 204
Temperature: 0°C to 55°C (normal operation)
-50°C to 60°C (non-destructive)
EMC
EN 55 022, class B
EN 61000-4-2,3,4,5
IEC 950/EN 60950
UL 1950
BML231204
Analog
Opto
Dimensions in mm
www.astec.com
181